Multifunctional earthing resistance meter
With the use of the presented earth resistance and soil resistivity meter Sonel MRU-120 it is possible to carry out earth resistance measurements using 3-pole and 4-wire method, measurements with the use of additional clamps (multiple earthing - without the necessity of unfastening the monitoring connections), as well as measurements using two-clamp method - in some cases it is possible to carry out the measurement without the necessity of using auxiliary probes driven into the ground. Sonel MRU-120 is a device designed to meet the needs of the power industry and used for earthing measurements - measuring range (measurements in accordance with EN 61557 standard) from 0.30 Ω. The functionality of the device is completed by the possibility to measure the resistivity of soil and the continuity of protective and equalising connections.
Measurement functions | Measurement range | Display range | Resolution | Accuracy |
---|---|---|---|---|
Interference voltage | 0 V…100 V | 0 V…100 V | 1 V | ±(2% m.v. + 3 digits) |
Resistance of earth connection and equipotential bonding | 0.24 Ω…19.9 kΩ acc. to EN 61557-4 | 0.00 Ω…19.9 kΩ | from 0.01 Ω | from ±(2% m.v. + 2 digits) |
Earth resistance | ||||
3-pole and 4-wire method | 0.30 Ω…19.9 kΩ acc. to EN 61557-5 | 0.00 Ω…19.9 kΩ | from 0.01 Ω | from ±(2% m.v. + 2 digits) |
3-pole + clamp method | 0.44 Ω…1999 Ω acc. to EN 61557-5 | 0.00 Ω…1999 Ω | from 0.01 Ω | ±(8% m.v. + 3 digits) |
two-clamp method | 0.00 Ω…149.9 Ω | 0.00 Ω…149.9 Ω | from 0.01 Ω | from ±(10% m.v. + 3 digits) |
auxiliary electrodes resistance | 0 Ω…19.9 kΩ | 0 Ω…19.9 kΩ | from 1 Ω | ±(5% (RE +RH+RS) + 8 digits), but ≥10% RE |
Earth resistivity | 0.0 Ωm…999 kΩm | 0.0 Ωm…999 kΩm | from0.1 Ωm | Depends on the accuracy of the RE 4p measurement, but not less than ±1 digit |