Heavy-duty earthing and soil resistivity meter
The Sonel MRU-120HD earth resistance and soil resistivity meter is a robust and functional device characterised by particular resistance to difficult working conditions. It is not afraid of dust or mud and performs excellently even in areas where there is an increased risk of splashing.
With the use of the Sonel MRU-120HD meter it is possible to perform earth resistance measurements using the 3-pole and 4-wire method. The instrument also allows measurements to be made using additional clamps (multiple earthing - without the need to disconnect the monitoring connections) and measurements using the two-clamp method. In some cases, the measurement can be done without the use of auxiliary probes driven into the ground. Sonel MRU-120HD is a tool designed especially for earthing measurements in the power industry. Measuring range (measurements in accordance with EN 61557) from 0.30 Ω.
Other practical functions of the device are the ability to measure the resistivity of the ground and the continuity of protective and equalising connections.
Measurement functions | Measurement range | Display range | Resolution | Accuracy |
---|---|---|---|---|
Interference voltage | 0 V…100 V | 0 V…100 V | 1 V | ±(2% m.v. + 3 digits) |
Connection and equipotential bonding resistance | 0.24 Ω…19.9 kΩ acc. to EN 61557-4 | 0.00 Ω…19.9 kΩ | from 0.01 Ω | from ±(2% m.v. + 2 digits) |
Earth resistance | ||||
3-pole and 4-wire method | 0.30 Ω…19.9 kΩ acc. to EN 61557-5 | 0.00 Ω…19.9 kΩ | from 0.01 Ω | from ±(2% m.v. + 2 digits) |
3-pole + clamp method | 0.44 Ω…1999 Ω acc. to EN 61557-5 | 0.00 Ω…1999 Ω | from 0.01 Ω | ±(8% m.v. + 3 digits) |
two-clamp method | 0.00 Ω…149.9 Ω | 0.00 Ω…149.9 Ω | from 0.01 Ω | from ±(10% m.v. + 3 digits) |
auxiliary electrodes resistance | 0 Ω…19.9 kΩ | 0 Ω…19.9 kΩ | from 1 Ω | ±(5% (RE +RH+RS) + 8 digits), but ≥10% RE |
Earth resistivity | 0.0 Ωm…999 kΩm | 0.0 Ωm…999 kΩm | from0.1 Ωm | Depends on the accuracy of the RE 4p measurement, but not less than ±1 digit |